Please use this identifier to cite or link to this item: https://hdl.handle.net/10316/4090
DC FieldValueLanguage
dc.contributor.authorFisk, William J.-
dc.contributor.authorAlmeida, Aníbal T. de-
dc.date.accessioned2008-09-01T09:59:04Z-
dc.date.available2008-09-01T09:59:04Z-
dc.date.issued1998en_US
dc.identifier.citationEnergy and Buildings. 29:1 (1998) 35-45en_US
dc.identifier.urihttps://hdl.handle.net/10316/4090-
dc.description.abstractWith sensor-based demand-controlled ventilation (SBDCV), the rate of ventilation is modulated over time based on the signals from indoor air pollutant or occupancy sensors. SBDCV offers two potential advantages: better control of indoor pollutant concentrations, and lower energy use and peak energy demand. Based on theoretical considerations and on a review of literature, SBDCV has the highest potential to be cost-effective in applications with the following characteristics: (a) a single or small number of pollutants dominate so that ventilation sufficient to control the concentration of the dominant pollutants provides effective control of all other pollutants; (b) large buildings or rooms with unpredictable temporally variable occupancy or pollutant emission; and (c) climates with high heating or cooling loads or locations with expensive energy. At present, most SBDCV systems are based on monitoring and control of carbon dioxide (CO2) concentrations. There is a limited number of well-documented case studies that quantify the energy savings and the cost-effectiveness of SBDCV. The case studies reviewed suggest that in appropriate applications, SBDCV produces significant energy savings with a payback period typically of a few years.en_US
dc.description.urihttp://www.sciencedirect.com/science/article/B6V2V-3W0FYSW-6/1/0c7fac94cabbf9f62949647086597500en_US
dc.format.mimetypeaplication/PDFen
dc.language.isoengeng
dc.rightsopenAccesseng
dc.subjectDemand-controlleden_US
dc.subjectIndoor air qualityen_US
dc.subjectSensorsen_US
dc.subjectVentilationen_US
dc.titleSensor-based demand-controlled ventilation: a reviewen_US
dc.typearticleen_US
uc.controloAutoridadeSim-
item.openairecristypehttp://purl.org/coar/resource_type/c_18cf-
item.openairetypearticle-
item.cerifentitytypePublications-
item.grantfulltextopen-
item.fulltextCom Texto completo-
item.languageiso639-1en-
crisitem.author.researchunitISR - Institute of Systems and Robotics-
crisitem.author.parentresearchunitUniversity of Coimbra-
crisitem.author.orcid0000-0002-3641-5174-
Appears in Collections:FCTUC Eng.Electrotécnica - Artigos em Revistas Internacionais
Files in This Item:
File Description SizeFormat
filedfa9ada000a74ab8b7cb2300f2bec4f3.pdf1.31 MBAdobe PDFView/Open
Show simple item record

Page view(s) 50

514
checked on Apr 23, 2024

Download(s) 20

1,176
checked on Apr 23, 2024

Google ScholarTM

Check


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.